Standby Power(50Hz) 1520KW /1900KVA Prime Power(50Hz) 1392KW /1740KVA
General Features: Engine Mitsubishi S16R-PTA2 , Radiator 40OC max, fans are driven by belt, with safety guard 24V charge alternator Alternator: single bearing alternator IP23, insulation class H/H Absorber Dry type air filter, fuel filter, oil filter, pre-filter, coolant filter Main line circuit breaker Standard control panel Two12V batteries, rack and cable Ripple flex exhaust pipe, exhaust siphon, flange, muffler User manual
Voltage | HZ | Phase | COS¢ |
Standby Amps |
Standby
Ratings
(KW/KVA)
|
Prime Ratings
(KW/KVA)
|
254/440 | 50 | 3 | 0.8 | 2755 | 1680/2100 | 1520/1900 |
240/415 | 50 | 3 | 0.8 | 2921 | 1680/2100 | 1520/1900 |
230/400 | 50 | 3 | 0.8 | 3031 | 1680/2100 | 1520/1900 |
220/380 | 50 | 3 | 0.8 | 3190 | 1680/2100 | 1520/1900 |
Prime Power (PRP): Prime power is available for an unlimited number of annual hours in variable load
application, in accordance with GB/T2820(eqv ISO8528); A 10% overload capability is available for a period of
1 hour within a 12-hour period of operation.
Standby Power Rating (ESP): The standby power rating is applicable for supplying emergency power for the
duration of a utility power interruption. No overload, utility parallel or negotiated outage operation capability is
available at this rating.
Sales Promises FKSPower provides a full line of brand new and high quality products. Each and every unit is strictly factory tested. Warranty is according to our standard conditions: a, 15 months, counted on the day FKSPOWER sold to the first buyer; b, One year after installation; c, 1000 running hours (accumulated); subject to the earlier one. Service and parts are available from FKSPower or distributors in your location.